西門子S7-200 ModBus從站通訊程序
發布時間:2019-08-02 09:52:50來源:
說明:PLC從站,PC作主站,用ModBus協議進行通訊。PC機讀取PLCVW區的數據;PC機還讀取PLC內部I或者O地址的狀態。
///////////////////////////////////////
以下是PLC程序實現,方便貼出,已轉換為STL
TITLE=程序注釋
Network 1 // 網絡標題
// 在第一個循環周期內初始化Modbus從站協議
LD SM0.1
CALL SBR3, 1, 12, 9600, 0, 0, 128, 32, 1000, &VB0, M10.1, MB11
Network 2
// 在每個循環周期內執行Modbus 從站協議
LD SM0.0
CALL SBR1, M10.2, MB12
Network 3
LD SM0.0
MOVW AIW0, VW100
/I +54, VW100
MOVW AIW2, VW102
/I +54, VW102
MOVW AIW4, VW104
/I +54, VW104
MOVW AIW6, VW106
/I +54, VW106
Network 4
LD SM0.0
= Q0.0
Network 5
LD I0.0
= Q0.1
Network 6
LD I0.1
= Q0.2
///////////////////////////////////
以下是VB源碼
Option Explicit
Private Declare Function GetTickCount Lib “kernel32″ () As Long
Dim x1
Dim p11, p12, p13, p14, p15, p16, p17, p18
Function CRC16(data() As Byte) As String
Dim CRC16Lo As Byte, CRC16Hi As Byte ‘CRC寄存器
Dim CL As Byte, CH As Byte ‘多項式碼&HA001
Dim SaveHi As Byte, SaveLo As Byte
Dim i As Integer
Dim Flag As Integer
CRC16Lo = &HFF
CRC16Hi = &HFF
CL = &H1
CH = &HA0
For i = 0 To UBound(data)
CRC16Lo = CRC16Lo Xor data(i) ‘每一個數據與CRC寄存器進行異或
For Flag = 0 To 7
SaveHi = CRC16Hi
SaveLo = CRC16Lo
CRC16Hi = CRC16Hi 2 ‘高位右移一位
CRC16Lo = CRC16Lo 2 ‘低位右移一位
If ((SaveHi And &H1) = &H1) Then ‘如果高位字節比較后一位為1
CRC16Lo = CRC16Lo Or &H80 ‘則低位字節右移后前面補1
End If ‘否則自動補0
If ((SaveLo And &H1) = &H1) Then ‘如果LSB為1,則與多項式碼進行異或
CRC16Hi = CRC16Hi Xor CH
CRC16Lo = CRC16Lo Xor CL
End If
Next Flag
Next i
Dim ReturnData(1) As Byte
ReturnData(0) = CRC16Hi ‘CRC高位
ReturnData(1) = CRC16Lo ‘CRC低位
CRC16 = ReturnData
End Function
Private Sub About_Click()
frmAbout.Show
End Sub
Private Sub Form_Load() ‘初始化
Timer1.Enabled = False ‘定時器1無效
Timer1.Interval = 1000 ‘定時器1時間為1S
Timer2.Enabled = True ‘定時器2有效
Timer2.Interval = 1000 ‘定時器2時間為1S
Text1.Text = “”
Text2.Text = “”
Text3.Text = “”
Text4.Text = “”
Text5.Text = “”
Text6.Text = “”
Text8.Text = “”
Text10.Text = “”
MSComm1.CommPort = 1 ‘設定端口號
MSComm1.Settings = “9600,n,8,1″ ‘設定通訊波特率
MSComm1.InBufferSize = 1024 ‘接收緩沖器大小
MSComm1.OutBufferSize = 1024 ‘輸出緩沖器大小
MSComm1.InputMode = comInputModeBinary ‘以二進制傳輸
MSComm1.RThreshold = 1 ‘
MSComm1.SThreshold = 0
MSComm1.InputLen = 0 ‘讀取接收緩沖器所有字符
MSComm1.OutBufferCount = 0 ‘清空發送緩沖區
MSComm1.InBufferCount = 0 ‘清空接收緩沖區
If MSComm1.PortOpen = False Then
Command3.Caption = “打開串口”
Else
Command3.Caption = “關閉串口”
End If
End Sub
Private Sub Command1_Click()
Timer1.Enabled = True
End Sub
Private Sub Command2_Click() ‘退出程序,定時器1無效
Timer1.Enabled = False
Cls
Unload Me
End Sub
Private Sub Command3_Click()
On Error Resume Next
If MSComm1.PortOpen = False Then
MSComm1.PortOpen = True
Else
MSComm1.PortOpen = False
End If
If MSComm1.PortOpen Then ‘打開關閉按鈕顯示文字
Command3.Caption = “關閉串口”
Else
Command3.Caption = “打開串口”
End If
If Err Then ‘打開串口失敗,則顯示出錯信息
MsgBox Error$, 48, “錯誤信息”
Exit Sub
End If
End Sub
Private Sub Timer1_Timer() ‘讀V存儲區數據
Dim CRC() As Byte
Dim FGetData As String
Dim aa() As Byte
Dim s As String
Dim str As String
Dim i As Integer
Dim bb, cc As String
ReDim aa(5) As Byte ‘定義動態數組
aa(0) = &HC
aa(1) = &H3
aa(2) = &H0
aa(3) = &H32
aa(4) = &H0
aa(5) = &H4
CRC = CRC16(aa)
str = CRC
s = “”
For i = 1 To LenB(str)
s = s + Hex(AscB(MidB(str, i, 1)))
Next i
bb = Right(s, 2)
cc = Mid(s, 1, 2)
If Len(s) < 4 Then
cc = Mid(s, 1, 1)
End If
ReDim Preserve aa(0 To 7) As Byte
aa(6) = Val(“&H” & bb)
aa(7) = Val(“&H” & cc)
MSComm1.OutBufferCount = 0 ‘清空輸出寄存器
MSComm1.Output = aa
FGetData = ReceiveData
Text5.Text = FGetData
p11 = Val(“&H” & Mid(FGetData, 7, 4))
p12 = Val(“&H” & Mid(FGetData, 11, 4))
p13 = Val(“&H” & Mid(FGetData, 15, 4))
p14 = Val(“&H” & Mid(FGetData, 19, 4))
End Sub
Private Sub Command4_Click() ‘I狀態
Dim CRC() As Byte
Dim FGetData As String
Dim aa() As Byte
Dim s As String
Dim str As String
Dim i As Integer
Dim bb, cc As String
ReDim aa(5) As Byte ‘定義動態數組
aa(0) = &HC
aa(1) = &H2
aa(2) = &H0
aa(3) = &H0
aa(4) = &H0
aa(5) = &H1
CRC = CRC16(aa)
str = CRC
s = “”
For i = 1 To LenB(str)
s = s + Hex(AscB(MidB(str, i, 1)))
Next i
bb = Right(s, 2)
cc = Mid(s, 1, 2)
If Len(s) < 4 Then
cc = Mid(s, 1, 1)
End If
ReDim Preserve aa(0 To 7) As Byte
aa(6) = Val(“&H” & bb)
aa(7) = Val(“&H” & cc)
MSComm1.OutBufferCount = 0 ‘清空輸出寄存器
MSComm1.Output = aa
FGetData = IReceiveData
p17 = Val(“&H” & Mid(FGetData, 7, 2))
p18 = Val(“&H” & Mid(FGetData, 9, 2))
End Sub
Private Sub Command5_Click() ‘Q狀態
Dim CRC() As Byte
Dim FGetData As String
Dim aa() As Byte
Dim s As String
Dim str As String
Dim i As Integer
Dim bb, cc As String
ReDim aa(5) As Byte ‘定義動態數組
aa(0) = &HC
aa(1) = &H1
aa(2) = &H0
aa(3) = &H0
aa(4) = &H0
aa(5) = &H1
CRC = CRC16(aa)
str = CRC
s = “”
For i = 1 To LenB(str)
s = s + Hex(AscB(MidB(str, i, 1)))
Next i
bb = Right(s, 2)
cc = Mid(s, 1, 2)
If Len(s) < 4 Then
cc = Mid(s, 1, 1)
End If
ReDim Preserve aa(0 To 7) As Byte
aa(6) = Val(“&H” & bb)
aa(7) = Val(“&H” & cc)
MSComm1.OutBufferCount = 0 ‘清空輸出寄存器
MSComm1.Output = aa
FGetData = QReceiveData
p15 = Val(“&H” & Mid(FGetData, 7, 2))
p16 = Val(“&H” & Mid(FGetData, 9, 2))
End Sub
Private Function ReceiveData() As String ‘返回V存儲器區數據
Dim FGetData As String
Dim t1 As Long
Dim av As Variant
Dim i As Integer
Dim ReDataLen As Integer
FGetData = “”
t1 = GetTickCount() ‘取時間,做延時用
Do ‘循環等待接收數據
DoEvents
If MSComm1.InBufferCount > 0 Then ‘串口有數據了
ReDataLen = MSComm1.InBufferCount ‘取數據長度
av = MSComm1.Input ‘將串口數據取出來
For i = 0 To ReDataLen ? 1
FGetData = FGetData & Right(“00″ & Hex(av(i)), 2)
Next i
End If
If Len(FGetData) >= 6 Then
If Len(FGetData) > Val(“&H” & Mid(FGetData, 5, 2)) * 2 + 8 Then
ReceiveData = FGetData
Exit Function
End If
End If
If GetTickCount ? t1 > 2000 Then ’2秒沒收完就不收了
ReceiveData = “”
Exit Function
End If
Loop
End Function
Private Function IReceiveData() As String ‘反回I狀態
Dim FGetData As String
Dim t1 As Long
Dim av As Variant
Dim i As Integer
Dim ReDataLen As Integer
FGetData = “”
t1 = GetTickCount() ‘取時間,做延時用
Do ‘循環等待接收數據
DoEvents
If MSComm1.InBufferCount > 0 Then ‘串口有數據了
ReDataLen = MSComm1.InBufferCount ‘取數據長度
av = MSComm1.Input ‘將串口數據取出來
For i = 0 To ReDataLen ? 1
FGetData = FGetData & Right(“00″ & Hex(av(i)), 2)
Next i
End If
If Len(FGetData) >= 6 Then
If Len(FGetData) > Val(“&H” & Mid(FGetData, 5, 2)) * 2 + 8 Then
IReceiveData = FGetData
Exit Function
End If
End If
If GetTickCount ? t1 > 2000 Then ’2秒沒收完就不收了
IReceiveData = “”
Exit Function
End If
Loop
End Function
Private Function QReceiveData() As String ‘反回Q狀態
Dim FGetData As String
Dim t1 As Long
Dim av As Variant
Dim i As Integer
Dim ReDataLen As Integer
FGetData = “”
t1 = GetTickCount() ‘取時間,做延時用
Do ‘循環等待接收數據
DoEvents
If MSComm1.InBufferCount > 0 Then ‘串口有數據了
ReDataLen = MSComm1.InBufferCount ‘取數據長度
av = MSComm1.Input ‘將串口數據取出來
For i = 0 To ReDataLen ? 1
FGetData = FGetData & Right(“00″ & Hex(av(i)), 2)
Next i
End If
If Len(FGetData) >= 6 Then
If Len(FGetData) > Val(“&H” & Mid(FGetData, 5, 2)) * 2 + 8 Then
QReceiveData = FGetData
Exit Function
End If
End If
If GetTickCount ? t1 > 2000 Then ’2秒沒收完就不收了
QReceiveData = “”
Exit Function
End If
Loop
End Function
Private Sub Timer2_Timer()
x1 = x1 + 1
Text10.Text = str(x1)
Text1.Text = str(p11)
Text2.Text = str(p12)
Text3.Text = str(p13)
Text4.Text = str(p14)
Text7.Text = str(p15)
If Text7.Text = 1 Then Text7.BackColor = RGB(255, 0, 255)
If Text7.Text = 0 Then Text7.BackColor = RGB(0, 255, 255)
‘Text6.Text = str(p16)
Text9.Text = str(p17)
If Text9.Text = 1 Then Text9.BackColor = RGB(255, 0, 255)
If Text9.Text = 0 Then Text9.BackColor = RGB(0, 255, 255)
‘Text8.Text = str(p18)
End Sub
新鄉變頻器維修,鶴壁變頻器維修,安陽變頻器維修,濮陽變頻器維修,焦作變頻器維修,濟源變頻器維修,洛陽變頻器維修,三門峽變頻器維修,開封變頻器維修,許昌變頻器維修,周口變頻器維修,商丘變頻器維修,漯河變頻器維修,平頂山變頻器維修,信陽變頻器維修,南陽變頻器維修,駐馬店變頻器維修 ,山西變頻器維修,山東變頻器維修等鄭州變頻器維修中心 變頻器維修中心,技術精湛,質量可靠,價格比較低,信譽保證! 維修電話:0371- 56700815 15515598858 鄭州變頻器 網址:http://www.cntjjp.com.cn